Learning Advanced Features
Auto-Tuning Default Settings
Rated Slip
Frequency
(Rpm)
Auto Tuning Parameter Setting Details
Select one of the auto tuning options and then press the [ENT] key to run the auto
tuning.
Auto tuning function is not enabled. If the auto tuning
function is ran, this will indicate that the auto tuning is
complete.
Measures all motor parameters, including stator
resistance (Rs), leakage inductance (Lsigma), stator
inductance (Ls), no-load current (Noload Curr), and
rotor time constant (Tr) while the motor is rotating.
As the motor is rotating, if the load is connected to the
motor, the parameters may not be measured
accurately. For accurate measurements, remove the
load attached to the motor. However, note that the
rotor time constant (Tr) must be measured in a
stopped position.
Measures all parameters while the motor is in the
stopped position. Measures stator resistance (Rs),
leakage inductance (Lsigma), stator inductance (Ls),
no-load current (Noload Curr), and rotor time constant
(Tr).