Multi-function (digital) Input Terminal Control Setting Details
Select whether or not to activate the time values set at In.85 and In.86
to selected terminals. If the terminal is not enabled, the time values
are set to the default values. If enabled, the set time values at In.85
and In.86 apply to the corresponding terminals.
Disable state of terminal
In.85 DI On Delay
In.86 DI Off Delay
Set the delay times for the selected terminals in In.84. When the
terminal receives a change of state input it is recognized as On or Off
after the set time.
Select terminal contact types for each input terminal. The position of
the lit segment corresponds to an “A” or “B” type contact input. With
the bottom segment on, it indicates that the terminal is configured as
an A terminal (Normally Open) contact. With the top segment on, it
indicates that the terminal is configured as a B terminal (Normally
Closed) contact. Terminals are numbered P5–P1, from right to left.
Select whether to use the Fx and Rx terminals as NO (Normal Open)
only or to use as NO (Normal Open) or NC (Normal Close). If set to 1:
NO only, the Fx and Rx terminals cannot be set as NC. If set to 0:
NO/NC, the Fx and Rx terminals also be set as NC.
Display the status of each contact. When a digital input is configured
as an “A” type terminal using dr.87, the On (closed) condition is
indicated by the top segment turnedg on. The Off condition is
indicated when the bottom segment is turned on. When a digital
input is configured as a “B” type terminal, the segment lights behave
conversely. Terminals are numbered P5–P1, from right to left.
Bit On when A contact
input is closed
Bit Off when A contact input
is open