Learning Advanced Features
Relay changes state when the output frequency is within
the frequency bandwidth (OU.58) centered around the
detection frequency (OU.57).
Conditions are: Absolute value (output frequency–
operating frequency) < frequency bandwidth/2
Example: Detection frequency (OU.57) is 30 Hz.
Frequency bandwidth (OU.58) is 10 Hz. Relay changes
state when the output frequency is between 25 Hz. and
35 Hz.
Realy changes state based on separate conditions for
acceleration and deceleration.
• During acceleration: Output frequency
Detection frequency
• During deceleration: Output frequency >
(Detection frequency–Frequency bandwidth/2)
Example: Detection frequency (OU.57) is 30 Hz.
Frequency bandwidth (OU.58) is 10 Hz. During
acceleration, relay changes state when output frequency
reaches detection frequency. During deceleration, the
relay changes state when the output frequency is below
the frequency bandwidth/2.
Relay changes state when inverter trips on motor
overload.
Relay changes state when inverter trips on inverter
overload.
Relay changes state when inverter trips on motor
underload.
Relay changes state to provide a fan fault warning.
Relay changes state when the inverter detects a motor
stall condition.
Relay changes state when the inverter trips on Over
Voltage.