RS-485 Communication Features
890054-00-00
GM2 Series VFD
194
Comm.
Address
Parameter
Scale
Unit
R/W
Assigned Content by Bit
B3
Reserved
B2
Reserved
B1
Relay 2
B0
Relay 1
0h0012
V1
0.01
%
R
V1 voltage input
0h0013
V0
0.01
%
R
Volume voltage input
0h0014
I2
0.01
%
R
I2 current input
0h0015
Motor rotation speed
1
Rpm
R
Displays existing motor rotation
speed
0h0016
- 0h0019
Reserved
-
-
-
-
0h001 A
Select Hz/rpm
-
-
R
0: Hz, 1: Rpm
0h001B
Display the number of
poles for the selected
motor
-
-
R
Display the number of poles for the
selected motor

Table of Contents