Table of Functions
234
GM2 Series VFD
890054-00-00
Code
Comm.
Address
Name
Setting Range
Initial
Value
Property*
V/F
SL
Ref.
Pr.19
0h1B13
Overload
warning time
0.030.0 (s)
10
O
O
O
p.156
Pr.20
0h1B14
Motion at
overload
fault
0
None
1: Free-
Run
O
O
O
p.156
1
Free-Run
2
Dec
Pr.21
0h1B15
Overload
fault level
30200 (%)
150
O
O
O
p.156
Pr.22
0h1B16
Overload
fault time
0.060.0 (s)
60
O
O
O
p.156
Pr.25
0h1B19
Under load
warning
selection
0
No
0: No
O
O
O
p.169
1
Yes
Pr.26
0h1B1 A
Under load
warning time
0.0600.0 (s)
10
O
O
O
p.169
Pr.27
0h1B1B
Under load
fault
selection
0
None
0: None
O
O
O
p.169
1
Free-Run
2
Dec
Pr.28
0h1B1C
Under load
fault time
0.0600.0 (s)
30
O
O
O
p.169
Pr.29
0h1B1D
Under load
lower limit
level
10100 (%)
30
O
O
O
p.169
Pr.30
0h1B1E
Under load
upper limit
level
10100 (%)
30
O
O
O
p.169
Pr.31
0h1B1F
No motor
motion at
detection
0
None
0: None
O
O
O
p.174
1
Free-Run
Pr.32
0h1B20
No motor
detection
current level
1100 (%)
5
O
O
O
p.174
Pr.33
0h1B21
No motor
detection
time
0.110.0 (s)
3
O
O
O
p.174
Pr.40
0h1B28
Electronic
thermal fault
selection
0
None
1: Free-
Run
O
O
O
p.154
1
Free-Run
2
Dec
Pr.41
0h1B29
Motor
cooling fan
type
0
Self-cool
0: Self-
cool
O
O
O
p.154
1
Forced-cool
Pr.42
0h1B2A
Electronic
thermal 1
minute rating
120200 (%)
150
O
O
O
p.154
Pr.43
0h1B2B
Electronic
thermal
continuous
rating
50150 (%)
115
O
O
O
p.154
Pr.45
0h1B2D
BX trip mode
0
Free-Run
0
X
O
O
p.172
1
Dec
Pr.50
0h1B32
Stall
bit
00001111
0
X
O
X
p.158

Table of Contents