Technical Specification
890054-00-00
256
GM2 Series VFD
Items
Description
acc/dec/stop
Exit PID Operation
Output
Multi-
function
relays
Programmable Output Relays
AC 250 V, 1 A
DC 30V, 1A
Relay 1 (A1-C1-B1)
Relay 2 (A2-C2)
Analog
output
012 VDC: Programmable Analog Output
Protection
Trip
Motor Overload
Under Torque
Motor Under Load
Inverter Over Heat
Over Current (OC1)
Short Circuit (OC2)
Over Voltage
External Trip
Low Voltage
Hardware Fault
Ground Fault
Temperature Sensor (NTC)
Motor Over Heat (Eth)
Fan Fault
Phase Open (In/Out)
Pre-PID Operation Failure
Inverter Overload
External Brake Trip
No Motor Trip
Reference Loss
Over Torque
Option Board trip
Alarm
Warnings: Reference Loss, Motor Overload, Motor Under Load,
Inverter Overload, Fan, Dynamic Braking Rate Warning, Auto
Tuning Error, Inverter Overheat
Instantaneous
Power Outage
Normal Duty: Less the 8ms (~1/2 cycle)
Heavy Duty: Less than 15 ms (~ 1 cycle)
For longer outages use KEB operation and/or Auto Restart
operation
Structure /
Working
Environment
Cooling type
Forced fan cooling structure
Protection
structure
IP 20, UL Open Type
UL Enclosed Type 1 is achieved with conduit box installation
(option)*
Ambient
Operating
temperature
14°F ~ +104°F (-10°C ~ +40)
Derating: 2% output amps for every degree above 104°F (40°C),
maximum 122°F (50°C)
No ice or frost should be present
Ambient humidity
Less than 95% RH (avoid condensation forming)
Storage
temperature
-4°F ~ +149°F (-20 ~ +65)
Environmental
factors
Prevent contact with corrosive gases, inflammable gases, oil
stains, dust, and other pollutants (Pollution Degree 2 Environment).
Operation
altitude/vibration
3280 ft (1,000 m).
Apply derating of 1% voltage/output current for every 100 m above
1,000 m, maximum of 4,000 m
Less than 9.8 m/sec
2
(1G).
Air pressure
15 PSI (70 ~106 kPa)