Programmable Output Relays
0–12 VDC: Programmable Analog Output
• Temperature Sensor (NTC)
• Pre-PID Operation Failure
Warnings: Reference Loss, Motor Overload, Motor Under Load,
Inverter Overload, Fan, Dynamic Braking Rate Warning, Auto
Tuning Error, Inverter Overheat
Instantaneous
Power Outage
Normal Duty: Less the 8ms (~1/2 cycle)
Heavy Duty: Less than 15 ms (~ 1 cycle)
For longer outages use KEB operation and/or Auto Restart
operation
Structure /
Working
Environment
Forced fan cooling structure
UL Enclosed Type 1 is achieved with conduit box installation
(option)*
Ambient
Operating
temperature
14°F ~ +104°F (-10°C ~ +40)
Derating: 2% output amps for every degree above 104°F (40°C),
maximum 122°F (50°C)
No ice or frost should be present
Less than 95% RH (avoid condensation forming)
-4°F ~ +149°F (-20℃ ~ +65℃)
Prevent contact with corrosive gases, inflammable gases, oil
stains, dust, and other pollutants (Pollution Degree 2 Environment).
Operation
altitude/vibration
Apply derating of 1% voltage/output current for every 100 m above
1,000 m, maximum of 4,000 m
Less than 9.8 m/sec
2
(1G).