Technical Specification
890054-00-00
264
GM2 Series VFD
Derating based on Carrier Frequency
The continuous rated current of the inverter is limited based on the carrier frequency setting.
Parameter Cn.04 allows for adjustment of the carrier frequency. The default setting is 2 kHz or 3
kHz depending on Load type (Normal or Heavy). Refer to the following table for derating of output
current for carrier frequency settings above 4 kHz.
Inverter Capacity
Current Derating %
Normal Duty
Heavy Duty
Carrier Frequency (kHz.)
kW
HP
kW
HP
1~4
5~6
9
12
15
3-phase
240V
0.75
1
0.4
0.5
100
100
91
81
72
1.5
2
0.75
1
100
100
91
81
72
2.2
3
1.5
2
100
100
91
81
72
4
5
2.2
3
100
100
91
81
72
5.5
7.5
4
5
100
93
83
73
62
7.5
10
5.5
7.5
100
93
83
73
62
11
15
7.5
10
100
91
79
69
58
3-phase
480V
0.75
1
0.4
0.5
100
100
91
81
72
1.5
2
0.75
1
100
100
91
81
72
2.2
3
1.5
2
100
100
91
81
72
4
5
2.2
3
100
100
91
81
72
5.5
7.5
4
5
100
100
85
70
58
7.5
10
5.5
7.5
100
93
83
73
62
11
15
7.5
10
100
89
72
59
48