10.7 Putting relay outputs into operation
10.7.1 Setting the parameters of a relay output
Example:
A disabled relay with latching is to be changed from a normal position of
<normally energised> to <normally de-energised> without latching. The relay
is also to be changed in monitoring from <disabled> to <enabled>.
Block level
NEXT
NEXT
NEXT
NEXT
NEXT (until the Relay block appears)
ENTER BUTTON
RELAY 01
NEXT
RELAY 01
NEXT
RELAY 01
NEXT
RELAY 01
ENTER BUTTON
Normal position
NEXT
Normal position
Normally de-
ENTER BUTTON
RELAY 01
NEXT
RELAY 01
ENTER BUTTON
Latching
NEXT
Latching
No
ENTER BUTTON
RELAY 01