VC-6000
TM
Compact monitor Part D Setting of limit setpoints and time delays
- 34 - C100585.002 Communication Vers. 03 © VC-6000
TM
Compact monitor Dec 09
10.7 Putting relay outputs into operation
10.7.1 Setting the parameters of a relay output
Example:
A disabled relay with latching is to be changed from a normal position of
<normally energised> to <normally de-energised> without latching. The relay
is also to be changed in monitoring from <disabled> to <enabled>.
Block level
USER MENU
NEXT
DATE & TIME
NEXT
SYSTEM
NEXT
LOGBOOK
NEXT
SENSOR 01
NEXT (until the Relay block appears)
RELAY 01
ENTER BUTTON
RELAY 01
Socket no.
NEXT
RELAY 01
Channel no.
NEXT
RELAY 01
Reset
NEXT
RELAY 01
Normal position
ENTER BUTTON
Normal position
Normally energised
NEXT
Normal position
Normally de-
energised
ENTER BUTTON
RELAY 01
Normal position
NEXT
RELAY 01
Latching
ENTER BUTTON
Latching
Yes
NEXT
Latching
No
ENTER BUTTON
RELAY 01
Latching