Setting of limit setpoints and time delays Part D VC-6000
TM
Compact monitor
© VC-6000
TM
Compact monitor Dec 09 C100585.002 Communication Vers. 03 - 33 -
10.6.2 Setting the parameters of a non-linear DC output
The procedure is in principle identical to that of setting the parameter of a
DC output with a linear output curve. The difference lies in the number of
anchor points to be defined on the curve that represents the output. A non-
linear DC output (curve with at least one bend) requires at least three anchor
points that must be set up with the value pairs (X1,Y1), (X2,Y2) and (X3,Y3).
A detailed explanation of the DC output can be read up in section C of the
signal-flow chart components