Logbook Part D VC-6000
TM
Compact monitor
© VC-6000
TM
Compact monitor Dec 09 C100585.002 Communication Vers. 03 - 43 -
Logbook full No further events will be recorded lOGBOOK
Power on The power supply was switched
on.
Setup false Storing configuration data failed.
All parameter settings must be
examined
USER MENU
Input b.false The combination of measurement
range and sensitivity that was
selected requires an input voltage
that is too high for the AD-
converter.
SENSOR ##,
SENSOR (A/B)##
Note:
The 2-digit number that follows the clear text entry in the logbook gives the
number of the block that originated the message. When more than one block
is responsible for the message, then the extension number does not
represent the number of the responsible block but for the socket position in
the Base board of the responsible module.
11.6.4 What to do when the Logbook is full?
How can you recognize that the Logbook is full?
When you can see that no further current entries are appearing in the
Logbuch you should page approx. 20 entries back in the Logbook. If a
message “Logbook full” is found further storage space must be created.
How can storage space be created in the Logbook for new messages?
There are three possibilities:
1. Switch the VIBROCONTROL 6000 Compact monitor off and then on
again.
After the switch-on set up the date and time once more!
2. Change a parameter and save the change when logging off.
The parameter LANGUAGE is suggested since this has no active
influence on the monitoring function.
3. Send via OPC the command RESET to the
VIBROCONTROL 6000 Compact monitor.
In all cases during the loading process of the system the monitoring activity
will be interrupted for a few seconds. After the load process is completed
there will be sufficient space in the Logbook for approx. 10,000 new
messages.