VC-6000
TM
Compact monitor Part B 2-channel input module for current / voltage
- 30 - C100584.002 Module Vers. 08 © VC-6000
TM
Compact monitor Nov. 2014
5 2-channel input module for current /
voltage
5.1 Function
♦ The input module for general current and
voltage signals, abbreviated to GP-TIM (General Purpose Transducer
Interface Module) is laid out for two measuring channels.
♦ Input signals of the type DC current (e.g. 4 - 20 mA), DC voltage
(e.g. 0 - 10 V), or dynamic voltage signals (-15 to +15 V) can be
processed. Selection of the desired input signal is done per channel
through the corresponding connection layout and the matching configu-
ration through the dialogue with the User-Terminal.
♦ A GP-TIM has no sensor power available, i.e. all input signals must be
active signals.
♦ The input module is managed internally through a Sensor(A/B) block
(Firmware), i.e. GP-TIM and Sensor(A/B) block together form a physical
interface between the VIBROCONTROL 6000 Compact monitor and the
outside world. The measured signal from the connected sensor is
acquired and made available to the signal path for further processing
and evaluation.
♦ A GP-TIM combines the following hardware functions:
• Diffential input amplifier
• Input selection switch
• Signal amplifier
• LED signalling
5.2 Technical data
5.2.1 Electrical properties
Input:
Voltage range -14 V ... + 14 V
Current range -30 mA … + 30 mA
Frequency range of input signal > 0 ... 50 kHz
Input impedance 200 kΩ (with voltage)
Working resistance 100 Ω (with current)
Sensor Sensitivity analogue adjustable
Amplification 1 (6 1 %)