124 en | Installation Modular Fire Panel
F.01U.028.089 | 8.0 | 2011.07 System Description Bosch Sicherheitssysteme GmbH
4.9.14 RML 0008 A Relay Module for Low Voltage
Relay module for low voltage with eight changeover relays (type C relays) for connecting
external elements e.g. notification appliances, smoke dampers etc.
Each relay has one NO (normally open) and one NC (normally closed) contact.
The maximum permissible contact load is 30 V DC/1 A.
Figure 4.78 RML 0008 A Relay Module for Low Voltage
The technical data can be found in Section 7.5.13 RML 0008 A Relay Module for Low Voltage,
page 164.
Labeling Connection
NO1 | C1 | NC1 Relay 1
NO2 | C2 | NC2 Relay 2
NO3 | C3 | NC3 Relay 3
NO4 | C4 | NC4 Relay 4
NO5 | C5 | NC5 Relay 5
NO6 | C6 | NC6 Relay 6
NO7 | C7 | NC7 Relay 7
NO8 | C8 | NC8 Relay 8