32 en | Planning Modular Fire Panel
F.01U.028.089 | 8.0 | 2011.07 System Description Bosch Sicherheitssysteme GmbH
3.4 Detection Points
Each element or input that can trigger an alarm after programming requires its own detection
point. Detection points are enabled via address cards. One FPA-5000 manages up to 4096
detection points.
All elements and inputs that do not use the "Input" type in the "Message type" setting are
regarded as detection points.
Therefore, all elements and inputs for which one of the following settings is programmed as
the "Message type" are regarded as detection points:
–Fire
–Internal fire
– Building control
– Multi-criterion
–Smoke
–Fault
–Heat
– Water
Only some of these message types are available for selection depending on the element type.
The elements and inputs that can trigger an alarm include all manual and automatic detectors,
as well as the modules and interface modules listed below on the basis of the available inputs.
The ENO 0000 B Fire Service Interface Module only requires a detection point when an FSE
release element is connected and has been programmed with the FSP-5000-RPS control panel
software.
No detection points need to be taken into account for the following interface modules:
FLM-420-NAC, FLM-420-RHV, FLM-420-RLV1, FLM-420-RLV8, FLM-420-O2.
No notification appliances or any of the outputs occupy detection points.
Modules: CZM 0004 A Up to 4 detection points (1 detection point per zone)
IOP 0008 A Up to 8 detection points
(1 detection point per monitored input)
Interface
modules:
FLM-420/4CON Up to 2 detection points
FLM-420-I8R1 Up to 8 detection points
FLM-420-I2 Up to 2 detection points
FLM-420-O8I2 Up to 2 detection points
FLM-420-O1I1 Up to 1 detection point
FLM-420-RLE Up to 2 detection points