EasyManuals Logo

Bosch FPA-5000 System Description

Bosch FPA-5000
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #148 background imageLoading...
Page #148 background image
148 en | Commissioning Modular Fire Panel
F.01U.028.089 | 8.0 | 2011.07 System Description Bosch Sicherheitssysteme GmbH
5 Commissioning
5.1 Notes
Commissioning and the function test may only be carried out by authorized specialist
personnel.
Observe all country-specific testing and acceptance regulations.
A function test must be carried out before commissioning (see Section 5.4 Functional
Test).
Bosch Security Systems recommends at least one function test and one visual inspection
per year.
5.2 Documentation
The panel controller is supplied with a CD on which you will find the product documentation
(installation instructions, system description).
The current and full product documentation can also be found on the Internet at
www.boschsecurity.com.
The fire panel is configured on a PC using the FSP-5000-RPS programming software. The
programming software and the associated documentation can also be found on the CD
supplied with the FPA-5000. More recent versions of the software are available on the Internet
for those with access rights.
Information about the programming software is also included in the online help.
5.3 Quick Guide for Commissioning
1. Connect the panel to the power supply.
2. Connect the MPC Panel Controller to the PC (via USB). Make sure that the current
version of the FSP-5000-RPS programming software is installed on your PC.
3. Start the auto-configuration. Edit the configuration according to the requirements of the
fire detection system.
4. Load the configuration to the MPC Panel Controller.
5. Start the walktest.
6. Test the power supply (see Page 149)
7. Check the conventional and LSN functions (see Page 149).
8. Test all detection points and activations as programmed (see Page 149).
9. Read out the diagnosis file and save the file as a test log.

Table of Contents

Other manuals for Bosch FPA-5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch FPA-5000 and is the answer not in the manual?

Bosch FPA-5000 Specifications

General IconGeneral
Max Number of Detectors per Loop254
DisplayLCD
Network CapabilityYes
Power Supply24 V DC
Operating Temperature-5°C to +50°C
Communication PortsEthernet
Humidity Range95% non-condensing

Related product manuals