42 en | Planning Modular Fire Panel
F.01U.028.089 | 8.0 | 2011.07 System Description Bosch Sicherheitssysteme GmbH
3.9 Configuration of BCM Battery Controller Module
The panel can be powered by up to 8 BCM-0000-B Battery Controller Modules, each with its
own UPS 2416 A Universal Power Supply. Current consumption is equally distributed among
all battery controller modules.
Notes
The 24 V switch outputs may not be connected in parallel.
The total current for all connected components including the battery charge current may
not exceed 6 A.
The batteries connected to the BCM must all be of the same type and have identical
electrical properties.
The cable length at the switch outputs for faults may not exceed 3 meters.
The cables for the switch outputs for faults may only be routed inside the housing.
Information on installation of the BCM module can be found in Section 4.9.3 BCM-0000-B
Battery Controller Module, page 110.