48 en | Planning Modular Fire Panel
F.01U.028.089 | 8.0 | 2011.07 System Description Bosch Sicherheitssysteme GmbH
Figure 3.14 Redundant configuration
For installation reasons, only 42 modules can be programmed when configuring a redundant
panel. Without redundancy, 46 modules per panel are possible if one housing is set up with
the panel controller and 10 modules and three housings each with 12 modules.
Pos. Designation Description
1 MPC Redundant panel controller
2 PRS 0002 A Short panel rail (may not be occupied with modules)
3 CRP 0000 A Redundant MPC cable set
4 CPH 0006 A
or
MPH 0010 A
Redundant panel housing, additionally installed PRD 0004 A
Panel Rail Long (1 x in the CPH 0006 A or 2 x in the
MPH 0010 A) may be fitted with modules.
4
3
2
CPH 0006 A EPH 0012 A CPH 0006 A
CPH 0006 A EPH 0012 A CPH 0006 A
1
NOTICE!
In line with EN 54-2, a redundant panel controller must be used if there are more than 512
detectors connected.