Modular Fire Panel Installation | en 99
Bosch Sicherheitssysteme GmbH System Description F.01U.028.089 | 8.0 | 2011.07
Addressing and Settings in the Network
The following pages illustrate connections, addressing and the associated configuration via
DIP switches for different loop and bus topologies:
– Standalone panel
– Standalone panel, redundant
– Loop topology
– Loop topology with redundant panel
– Bus Topology
– Bus topology with redundant panel
– Bus topology with redundant network
– Bus topology with redundant network and redundant panel
The panels and remote keypads are identified in the network by a unique address. This
address is set on the rotary switches and is known as the rotary switch number (RSN) (see
the figures in the circle on the circuit diagrams). The rotary switches are located on the rear of
the panel controller (see Figure 4.50).
Note the address on the sign below the rotary switches (see Figure 4.50, step 2).
The DIP switches are located on the rear of the panel controller (see Figure 4.50).
Mark the selected setting on the sign above the DIP switches (see Figure 4.50, step 4).
NOTICE!
Redundant panels must have identical addresses.