Solution 6000-IP
Installation Manual Output Programming
8-9
Bosch Security Systems 10/22 BLCC615I
Panic, Module Tamper, Phone Line Fail, RF Receiver
Tamper/Missing/Jamming, Keypad Panic or Keypad
Medical emergency, Keypad/LAN Reader Tamper and
Door Forced events.
39 – Fire Alarm
This event type will cause the output to operate when
any audible fire zone or keypad emergency fire alarm
occurs. The output will reset when the system or area is
disarmed.
40 – Burglary Alarm
This event type will cause the output to operate when
any audible burglary alarm (including keypad emergency
panic, medical and tamper alarm) occurs. The output will
reset when the system or area is disarmed.
41 – Silent Alarm
This event type will cause the output to operate when
any silent alarm occurs (including silent fire and silent
keypad emergency alarms). The output will reset when
the system or area is disarmed.
42 – Duress Alarm
This event type will cause the output to operate when a
user initiates a Duress alarm.
43 – Keypad Medical
This event type will cause the output to operate when a
silent or audible medical alarm has been initiated from
the keypad. The output will reset when the system or
area is disarmed.
To initiate a medical emergency via the keypad,
simultaneously press and hold the [7] and [9] keys for 2
seconds.
44 – Keypad Fire
This event type will cause the output to operate when
a silent or audible fire alarm has been initiated from the
keypad. The output will reset when the system or area is
disarmed.
To initiate a fire emergency via the keypad,
simultaneously press and and hold the [4] and [6] keys
for 2 seconds.
45 – Keypad Panic
This event type will cause the output to operate when a
silent or audible panic alarm has been initiated from the
keypad. The output will reset when the system or area is
disarmed.
To initiate a panic emergency via the keypad,
simultaneously press and hold [1] and [3] keys.
46 – Device Tamper
This event type will cause the output to operate when
the tamper circuit on the rear of the keypad is triggered.
The output will reset when a valid user PIN is entered.
47 – Access Denied
This event type will trigger if you attempt to enter an
incorrect code more times than programmed in the pin
retry count location. The event assignment will be the
area number for this event type.
48 – Strobe
This event type is used to operate a stobe warning light.
The output can be made to operate when any of the
following events occur. At leaset one strobe event must
be selected for this output type to operate. See MENU
2-1-5 — Strobe Trigger option.
Strobe trigger options include:
= Audible Burglary Alarm
= Silent Burglary Alarm
= Fire Alarm
= Arm/Disarm Flash Via RF Keyfob
= Arm/Disarm Flash Via Keyswitch or PGM Input
= 24-Hour Alarm
49 – Smoke Sensor GND
This output is used to allow smoke detectors to be
automatically reset when the system is disarmed. You
should connect the GND terminal of all smoke detectors
in the system to outputs which are set to this event type.
For this output type to perform correctly you should
program the output polarity as type 11 - Normally
Low One Shot Open and program the output time
parameter to be 5 seconds. The smoke sensor needs to
be connected to a zone input programmed as fire.
If fire alarm verification is required, we recommend that
you program the zone pulse count tor 2 pulses and the
pulse count time to 90 seconds for each fire zone.
50 – Sensor Watch
This event type will cause the output to operate when
a zone sensor watch fault has occured. The output will
reset when the system or area is armed. See MENU 3-1-
8 — Zone Options in Section 7 - Input Programming for
more information on Sensor Watch.
51 – Senior Watch
This event type will cause the output to operate when
a Senior Watch fault has occured. See MENU 2-1-2 —
Input Options in Section 6 - Area Programming for more
information on Senior Watch.
52 – Exit Error
This event type will cause the output to operate when a
Entry/Exit Delay zone becomes unsealed during exit time
and remains unsealed when the exit time expires. The
output will reset when the system is disarmed.