Troubleshooting / FAQ
8
CLS Pro 600 – Line and Contrast Sensor 83/108
8 Troubleshooting / FAQ
Pos. Error Possible Cause Remedy
1
There is no synchronisation sig-
nal.
There is no connection
between sensor and control-
ler.
Check the connecting cable
and the connecting plugs.
2
The footer in the display of the
sensor is missing.
The controller is not paramet-
erised.
Carry out parameterization of
the controller.
3
During the guiding to the edge
of a line, the scanning jumps to
the second edge of the line.
The sensor settings are not
suitable for the job. Maybe
the wrong job has been
loaded.
Load the job DEFAULT.
4
After replacing the controller, all
indicators on the sensor display
flash. The frame of the display is
grey and the tool key is shown in
setup mode.
Wrong sensor software.
Install correct sensor soft-
ware.
5
ekrPro Com60 with CLS Pro 600:
In automatic mode, the blocking
signal (lock) appears in the dis-
play of the controller. No error is
displayed on the ekrPro Com60
and the remote control using
the CLS keyboard is okay.
Move rotary switch S1 to 1
on the ekrPro Com60 (see
commissioning on the CAN
Bus – Device Address).
Select and enter CLS:EMS 17
as the standard system.