Troubleshooting / FAQ
8
CLS Pro 600 – Line and Contrast Sensor 83/108
8 Troubleshooting / FAQ
Pos. Error Possible Cause Remedy
1
There is no synchronisation sig-
nal.
There is no connection
between sensor and control-
ler.
►
Check the connecting cable
and the connecting plugs.
2
The footer in the display of the
sensor is missing.
The controller is not paramet-
erised.
►
Carry out parameterization of
the controller.
3
During the guiding to the edge
of a line, the scanning jumps to
the second edge of the line.
The sensor settings are not
suitable for the job. Maybe
the wrong job has been
loaded.
►
Load the job DEFAULT.
4
After replacing the controller, all
indicators on the sensor display
flash. The frame of the display is
grey and the tool key is shown in
setup mode.
Wrong sensor software.
►
Install correct sensor soft-
ware.
5
ekrPro Com60 with CLS Pro 600:
In automatic mode, the blocking
signal (lock) appears in the dis-
play of the controller. No error is
displayed on the ekrPro Com60
and the remote control using
the CLS keyboard is okay.
►
Move rotary switch S1 to 1
on the ekrPro Com60 (see
commissioning on the CAN
Bus – Device Address).
►
Select and enter CLS:EMS 17
as the standard system.