ï‚· Increase the integrative factor slightly to achieve acceptable response to changes. Too small
an I-factor will cause an excessively slow response, while too high an I-factor will cause
overshooting or even oscillations.
NOTE:
It may be helpful to disable issuing the GCB close command when adjusting synchronization loops.
Adjust the setpoint Phase Window to 0 to disable it. Adjust the setpoint back to its original value after
the adjustment is finished.
CAUTION!
Be ready to press the emergency stop button in the event that the regulation loop starts to behave
unacceptably.