169
Setpoint: COM1 Mode
Group
Comms Settings
Range [units]
DIRECT, MODEM, MODBUS, ECU LINK [-]
Related
applications
All
Description
Communication protocol switch for the COM1 channel.
DIRECT: ComAp PC SW communication protocol via direct cable.
MODEM: ComAp PC SW communication protocol via modem.
MODBUS: Modbus protocol. Find a detailed description in a
separate chapter.
ECU LINK: Protocol for communication with EFI engines via
Modbus.
Setpoint: COM2 Mode
Group
Comms Settings
Range [units]
DIRECT, MODBUS, ECU LINK [-]
Related
applications
All
Description
Communication protocol switch for the COM2 channel.
DIRECT: ComAp PC SW communication protocol via direct cable.
MODBUS: Modbus protocol. Find a detailed description in a
separate chapter.
ECU LINK: Protocol for communication with EFI engines via
Modbus.
Setpoint: ModemIniString
Group
Comms Settings
Range [units]
[-]
Related
applications
All
Description
If your modem needs additional initialization AT commands (i.e. because of
national telephony network differences), they can be entered here.
Otherwise leave this setpoint blank.
Setpoint: ModbusComSpeed
Group
Comms Settings
Range [units]
9600, 19200, 38400, 57600 [bps]
Related
applications
All
Description
If the Modbus mode is selected on COM1 or COM2 channels, the Modbus
communication speed can be adjusted here.