Setpoint: GCB Open Del
Group
Sync/Load Ctrl
Range [units]
Load Ramp ... 1800 [s]
Related
applications
All
Description
Use this setpoint to adjust the timeout for reaching the load level GCB Open
Level during the gen-set is being unloaded. When the timeout has elapsed,
the GCB will open regardless of the load.
Setpoint: Sync Timeout
Group
Sync/Load Ctrl
Range [units]
1 ... 1800 [s]
Related
applications
All
Description
This setpoint adjusts the maximum duration of synchronizing. If
synchronizing is not successful within this period of time, the Sync Timeout
or RevSyncTimeout alarm will be issued.
Setpoint: LoadShare Gain
Group
Sync/Load Ctrl
Range [units]
0 ... 200.0 [%]
Related
applications
MINT
Description
Gain of the load sharing control PI loop.
Setpoint: LoadShare Int
Group
Sync/Load Ctrl
Range [units]
0 ... 100 [%]
Related
applications
MINT
Description
Relative integration factor of load sharing control loop.