InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
279
Alarm: Forward synchronization timeout
Alarm type
Breaker open & cool down
Alarmlist
message
Sync Timeout
Alarm evaluated
During GCB synchronization only
Related
applications
All
Description
If the synchronization of GCB (forward synchronization) is not successful
within a time period adjusted by the setpoint Sync Timeout, this alarm will be
issued, the gen-set will be cooled down and stopped.
Alarm: Reverse synchronization timeout
Alarm type
Warning
Alarmlist
message
RevSyncTimeout
Alarm evaluated
During MCB synchronization only
Related
applications
SPtM
Description
If the synchronization of MCB (reverse synchronization) is not successful
within a time period adjusted by the setpoint Sync Timeout, this alarm will be
issued and the gen-set will remain in island operation. A new attempt of
reverse synchronization can be initiated as soon as the alarm is reset.
Alarm: Generator overload
Alarm type
Breaker open & cool down
Alarmlist
message
BOC Overload
Alarm evaluated
All the time
Related
applications
All
Description
The behaviour of the overload alarm is adjusted by the following setpoints:
ï‚· Overload BOC adjusts the overload limit.
ï‚· Overload Del adjusts the delay.
The alarm is issued when the gen-set power is over the limit for time period
longer than the delay.

Table of Contents

Other manuals for ComAp InteliCompact NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliCompact NT and is the answer not in the manual?

ComAp InteliCompact NT Specifications

General IconGeneral
BrandComAp
ModelInteliCompact NT
CategoryController
LanguageEnglish

Related product manuals