212
Setpoint: #Time
Group
Date/Time
Range [units]
[hh.mm.ss]
Related
applications
All
Description
System time can be modified here. The system time is stored in a battery-
backup RTC circuit and does not normally need to be adjusted except for
initial setting and occasional corrections.
The system date and time is used for the exercise timers as well as for the
history log. Each record in the history log contains a date/time stamp.
NOTE:
If the system date and time become inaccurate after the controller has been
switched off for a long period of time, it may indicate that the backup battery
needs to be replaced.
Setpoint: #Date
Group
Date/Time
Range [units]
[dd.mm.yyyy]
Related
applications
All
Description
System date can be modified here. The system date is stored in a battery-
backup RTC circuit and does not normally need to be adjusted except for
initial setting.
The system date and time is used for the exercise timers as well as for the
history log. Each record in the history log contains a date/time stamp.
NOTE:
If the system date and time becomes incorrect after the controller has been
switched off for a long period of time, it may indicate that the backup battery
needs to be replaced.
Setpoint: Timer1 Repeat
Group
Date/Time
Range [units]
NONE, MONDAY, TUESDAY, ... SUNDAY, MON-FRI, MON-SAT, MON-
SUN, SAT-SUN [-]
Related
applications
All
Description
This setpoint adjusts the repetition period of the Timer 1. Learn more about
exercise timers in a separate chapter.