MarelliMotori Mark V (M16FA655A)
18VAC
From
generator
OUT1
OCOM
iG-
AVRi
230/400VAC
0VAC
AVRI
AO GND
AO GND
AVRI
P
Q
IG- AVRi
TRANS
AVRi trim to 1/4 position
Volt/PF ctrl:
AVR Bias = 15%
Mecc Alte SpA
Mecc Alte SpA: U.V.R.6
18VAC
From
generator
OUT2
OCOM
iG-
AVRi
230/400VAC
0VAC
AVRI
AO GND
AO GND
AVRI
IG-
AVRi
TRANS
AVRi output is connected instead of Remote voltage trimmer 100 KΩ
(OUT2= top position wire and GND = second position from top).
AVRi trim to maximum
clockwise.
Volt/PF ctrl:
AVR Bias = 75%
Mecc Alte SpA: S.R.7/2
18VAC
From
generator
OUT1
OCOM
iG-
AVRi
230/400VAC
0VAC
AVRI
AO GND
AO GND
AVRI
5B
7
IG-
AVRi
TRANS
AVRi trim to maximum
clockwise.
Volt/PF ctrl:
AVR Bias = 75%
Mecc Alte UVR
18VAC
From
generator
OUT1
OUT2
iG-
AVRi
230/400VAC
0VAC
AVRI
AO GND
8
6
AVRI
AO GND
IG-
AVRi
TRANS
AVRi trim to maximum
clockwise.
Volt/PF ctrl:
AVR Bias = 50%
Mecc Alte DER1