InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp May 2015
36
Basler: DESC 200
18VAC
From
generator
OUT1
OUT2
iG-
AVRi
230/400VAC
0VAC
AVRI
AO GND
A10
A9
AVRI
AO GND
IG-
AVRi
TRANS
AVRi trim to minimum counter
clockwise.
Volt/PF ctrl:
AVR Bias = 50%
Marathon
Marathon DVR2000E
18VAC
From
generator
OUT1
OUT2
iG-
AVRi
230/400VAC
0VAC
AVRI
AO GND
B
A
AVRI
AO GND
IG-
AVRi
TRANS
AVRi trim to 1/3 clockwise
Volt/PF ctrl:
AVR Bias = 50%
Marathon PM100, 200
18VAC
From
generator
OUT1
OUT2
iG-
AVRi
230/400VAC
0VAC
AVRI
AO GND
6
7
AVRI
AO GND
IG-
AVRi
TRANS
Volt/PF ctrl:
AVR Bias = 50%
Marelli
MarelliMotori Mark I (M40FA640A/A)
18VAC
From
generator
OUT1
OUT2
iG-
AVRi
230/400VAC
0VAC
AVRI
AO GND
8
6
AVRI
AO GND
IG-
AVRi
TRANS
Volt/PF ctrl:
AVR Bias = 50%
MarelliMotori (M40FA610A)
18VAC
From
generator
OUT1
OUT2
iG-
AVRi
230/400VAC
0VAC
AVRI
AO GND
8
6
AVRI
AO GND
IG-
AVRi
TRANS
Volt/PF ctrl:
AVR Bias = 50%