InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp May 2015
45
A1
I9
Cummins
ECPG
SG +
AO COM
Vout
Sync/Load Ctrl:
Speed Gov Bias = 5.00 V
SpeedGovChar =
POSITIVE
Pay attention to the connector and jumper orientation.
0V
5V
Cummins
ONAN
SG +
AO COM
VoutR
10k
Sync/Load Ctrl:
Speed Gov Bias = 5.00 V
SpeedGovChar =
POSITIVE
11
Cummins
EFC
SG +
AO COM
VoutR
8
4µ7/50V
200k
Sync/Load Ctrl:
Speed Gov Bias = 6.40 V
SpeedGovChar =
POSITIVE
SpeedGovLowLim = 5 V
SpeedGovHiLim = 7.8 V
Setting at 1500 RPM: Primary setting governor with disconnected speed regulation lines.
32
9
Cummins
QSL9
SG +
AO COM
Vout
Sync/Load Ctrl:
Speed Gov Bias = 3.50 V
SpeedGovChar =
POSITIVE
SpeedGovLowLim = 2.5 V
SpeedGovHiLim = 5 V
03-12
03-11
Cummins
GCS
SG +
AO COM
VoutR
Sync/Load Ctrl:
Speed Gov Bias = 5.00 V
SpeedGovChar =
POSITIVE
SpeedGovLowLim = 2.5 V
SpeedGovHiLim = 7.5 V