InteliDrive DCU Industrial 3.4.0 Global Guide
138
Load sharing
Setpoint group Load sharing Related FW 3.4.0
Range [units] 0.0 .. 200.0 [%]
Default value 5.0
Force value
Alternative config
Step 0.1
Comm object 8659 Related applications AS
Description
Relative Gain of the load sharing loop.
Load Gain
6 back to List of setpoints
Setpoint group Load sharing Related FW 3.4.0
Range [units] 0.0 .. 100.0 [%]
Default value 10.0
Force value
Alternative config
Step 0.1
Comm object 8713 Related applications AS
Description
Relative Integration factor of the load sharing loop.
Load Int
6 back to List of setpoints
Setpoint group Load sharing Related FW 3.4.0
Range [units] 0.0 .. 60.0 [s]
Default value 5
Force value
Alternative config
Step 0.1
Comm object 9949 Related applications AS
Description
Time between the clutch is switched on/off and the load sharing function is activated.