137
Setpoint group
RPMdep protection (AS
only)
Related FW 3.4.0
Range [units] 0 .. 600 [s]
Default value 10
Force value Alternative
config
Step 1
Comm object 10151 Related applications AS
Description
RPM dependent Coolant pressure protection delay. Corresponding protection is activated when Coolant
pressure is below limit for CoolPrRPMdel.
To activate RPM dependent coolant pressure protection any analog value has to be linked with COOLANT
PRESS (PAGE 235).
Note: RPM dependent coolant pressure protection is fix configured Protection block type = Engine
running only with RunOnlyBlkDel1 delay.
CoolPrRPMdel