EasyManua.ls Logo

ComAp InteliDrive DCU Industrial - Page 235

ComAp InteliDrive DCU Industrial
350 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliDrive DCU Industrial 3.4.0 Global Guide
235
Related FW 3.4.0 Related applications AS, SS
Comm object 7
Description
Analog input for external LCD brightness setting (e.g. via potentiometer). Keyboard LCD brightness setting
does not work when input is configured. Expected value is in the range 0 to 100%.
LCD Brightness
6 back to List of LAI
Related FW 3.4.0 Related applications AS, SS
Comm object 8
Description
RPM value from ECU - J1939.
Engine Speed
6 back to List of LAI
Related FW 3.4.0 Related applications AS, SS
Comm object 9
Description
Engine oil pressure, which is displayed at the first controller screen.
Note: Configure OIL PRESS (PAGE 235) (LAI card in DriveConfig) to display the value at the first
controller screen.
Oil Press
6 back to List of LAI
Related FW 3.4.0 Related applications AS, SS
Comm object 77
Description
Universal input for engine oil temperature.
Oil Temp
6 back to List of LAI
Related FW 3.4.0 Related applications AS
Comm object 66
Description
Running indication and speed dependable protection in PRP.
Coolant Press
6 back to List of LAI

Table of Contents