InteliDrive DCU Industrial 3.4.0 Global Guide
136
Setpoint group
RPMdep protection (AS
only)
Related FW 3.4.0
Range [units] 0.0 .. 10.0 [Bar]
Default value 0.0
Force value
Alternative config
YES
Step 0.1
Comm object 10145 Related applications AS
Description
Linear Warning characteristic is defined by two points for Idle RPM (page 118) and Nominal RPM (page
104). CPNomRPMWrn defines coolant pressure warning level at nominal speed. For details see
CoolPrRPMdel (page 137) description.
CPNomRPMWrn
6 back to List of setpoints
Setpoint group
RPMdep protection (AS
only)
Related FW 3.4.0
Range [units] 0.0 .. 10.0 [Bar]
Default value 0.0
Force value
Alternative config
Step 0.1
Comm object 10146 Related applications AS
Description
Linear Shutdown characteristic is defined by two points for Idle RPM (page 118) and Nominal RPM (page
104). CPIdleRPMSd defines coolant pressure shutdown level at idle speed. For details see CoolPrRPMdel
(page 137) description.
CPIdleRPMSd
6 back to List of setpoints
Setpoint group
RPMdep protection (AS
only)
Related FW 3.4.0
Range [units] 0.0 .. 10.0 [Bar]
Default value 0.0
Force value
Alternative config
Step 0.1
Comm object 10147 Related applications AS
Description
Linear Shutdown characteristic is defined by two points for Idle RPM (page 118) and Nominal RPM (page
104). CPNomRPMSd defines coolant pressure shutdown level at nominal speed. For details see
CoolPrRPMdel (page 137) description.
CPNomRPMSd
6 back to List of setpoints