InteliDrive DCU Industrial 3.4.0 Global Guide
135
Setpoint group
RPMdep protection (AS
only)
Related FW 3.4.0
Range [units] 0.. 600 [s]
Default value 10
Force value Alternative
config
Step 1
Comm object 10150 Related applications AS
Description
RPM dependent Oil pressure protection delay. Corresponding protection is activated when Oil pressure is
below limit for OilPrRPMdel.
To activate RPM dependent oil pressure protection any analog value has to be linked with OIL PRESS (PAGE
235).
Note: RPM dependent oil pressure protection is fix configured Protection block type = Engine running
only with RunOnlyBlkDel1 delay.
OilPrRPMdel
6 back to List of setpoints
Setpoint group
RPMdep protection (AS
only)
Related FW 3.4.0
Range [units] 0.0 .. 10.0 [Bar]
Default value 0.0
Force value
Alternative config
YES
Step 0.1
Comm object 10144 Related applications AS
Description
Linear Warning characteristic is defined by two points for Idle RPM (page 118) and Nominal RPM (page
104). CPIdleRPMWrn defines coolant pressure warning level at idle speed. For details see CoolPrRPMdel
(page 137) description.
CPIdleRPMWrn
6 back to List of setpoints