InteliDrive DCU Industrial 3.4.0 Global Guide
134
Setpoint group
RPMdep protection (AS
only)
Related FW 3.4.0
Range [units] 0.0 .. 10.0 [Bar]
Default value 0.0
Force value
Alternative config
Step 0.1
Comm object 10141 Related applications AS
Description
Linear Warning characteristic is defined by two points for Idle RPM (page 118) and Nominal RPM (page
104). OPNomRPMWrn defines oil pressure warning level at nominal speed. For details see OilPrRPMdel
description.
OPNomRPMWrn
6 back to List of setpoints
Setpoint group
RPMdep protection (AS
only)
Related FW 3.4.0
Range [units] 0.0 .. 10.0 [Bar]
Default value 0.0
Force value
Alternative config
Step 0.1
Comm object 10142 Related applications AS
Description
Linear Shutdown characteristic is defined by two points for Idle RPM (page 118) and Nominal RPM (page
104). OPIdleRPMSd defines oil pressure shutdown level at idle speed. For details see OilPrRPMdel (page
135) description.
OPIdleRPMSd
6 back to List of setpoints
Setpoint group
RPMdep protection (AS
only)
Related FW 3.4.0
Range [units] 0.0 .. 10.0 [Bar]
Default value 0.0
Force value
Alternative config
YES
Step 0.1
Comm object 10143 Related applications AS
Description
Linear Shutdown characteristic is defined by two points for Idle RPM (page 118) and Nominal RPM (page
104). OPNomRPMSd defines oil pressure shutdown level at nominal speed. For details see OilPrRPMdel
(page 135) description.
OPNomRPMSd
6 back to List of setpoints