InteliDrive DCU Industrial 3.4.0 Global Guide
190
Source: Log Bout
Related FW 3.4.0 Related applications AS, SS
Comm object 2
Description
The output is closed if there is a communication failure with any external terminal.
Note: When communication with any terminal is lost, the LBO: HORN (PAGE 193) is closed and a history
record is written. This history record can be enabled / disabled by the setpoint LB/UART Log (page
111).
Note: Communication failure of specific external terminal(s) is indicated by these outputs:
ACCESSLOCKCOM1 (PAGE 190)
ACCESSLOCKCOM2 (PAGE 191)
ACSLOCKCAN2(1) (PAGE 191)
ACSLOCKCAN2(2) (PAGE 191)
ACSLOCKCAN2(3) (PAGE 192)
ACSLOCKCAN2(4) (PAGE 192)
ACSLOCKCAN2(5) (PAGE 192)
AccessLock ext
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 2
Description
The output is closed if there is a communication failure with the controller front panel.
The timeout for communication failure is 5 seconds.
Note: When communication with any terminal is lost, the LBO: HORN (PAGE 193) is closed and a history
record is written. This history record can be enabled / disabled by the setpoint LB/UART Log (page
111).
AccessLock int
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 2
Description
The output is closed if there is a communication failure with the RS232 interface.
The timeout for communication failure is 5 seconds.
Note: When communication with any terminal is lost, the LBO: HORN (PAGE 193) is closed and a history
record is written. This history record can be enabled / disabled by the setpoint LB/UART Log (page
111).
AccessLockCOM1
6 back to List of LBO