InteliDrive DCU Industrial 3.4.0 Global Guide
206
Related FW 3.4.0 Related applications AS, SS
Comm object 280
Description
Indicates Ready state for Remote engine start.
RdyForRemStart
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 116
Description
The output closes at the beginning of prestart and opens if the engine shall be stopped. This output can be
used to indicate when the ECU should be powered up i.e. only while the engine is running.
This output also influences evaluation of communication failure with ECU and related alarms from analog
inputs read from the ECU. If the output is configured (which means configured on physical binary output or
VBOUT output), announcement of the communication error is blocked if the engine is switched off including
the stopping procedure as shown in the figure.
Note: The LBO must be configured on physical binary output or VBOUT output. It is not enough to
configure it as a PLC input for example.
Note: If the LBO: ECUPowerRelay is used to energize ECU unit during the start procedure, the
initialization of the ECU unit might take slightly longer time and Wrn CommError(x)/Sd CommError(x)
might appear. In this case is recommended to use ECUCOMFAILBLCK (PAGE 169), please see this LBI.
ECU PowerRelay
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 281
Description
1 sec pulse is generated after panel Start button is pressed.
StartButtEcho
6 back to List of LBO