InteliDrive DCU Industrial 3.4.0 Global Guide
205
Related FW 3.4.0 Related applications AS, SS
Comm object 61
Description
Output closes with binary output Prestart and opens with binary output Cooling pump (see AfterCoolTime
(page 121)
Operational
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 277
Description
Binary output Timer Active is closed and opened according to Timer setpoints setting. Engine starts and
stops when this output is connected (configured) to REM START/STOP (PAGE 180). Timer is active in all
controller modes include OFF mode.
Timer Active
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 278
Description
It follows the panel Red LED. Starts blink after any (Wrn, Sd) Alarm is activated, light after Fault reset,
disappear after Fault reset when no alarm is active.
Alarm BlinkAct
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 251
Description
Indicates any active protection configured as Shut down Override.
Common SdO
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 279
Description
Power derating indication, information received from communication bus.
Derating Alarm
6 back to List of LBO