InteliDrive DCU Industrial 3.4.0 Global Guide
204
Related FW 3.4.0 Related applications AS, SS
Comm object 274
Description
Inverted function to IDLE/NOMINAL (PAGE 197). The output closes during engine start, after Idle Time
setpoint elapses. The output closes again after Cooling Time is finished.
Nominal/Idle
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 275
Description
Function is based on COMMON ALARM (PAGE 194) - stays closed when any alarm is active (at least one item
in Alarm list) and opens for 2 sec when any new Alarm is activated. The first activation is delayed 2 sec. No
Fault reset influence when at least one alarm is active. Output opens when Alarm list is empty.
Alarm Blink
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 276
Description
The output is closed when Idle/Nominal (page 105) = NOMINAL or Idle/Nominal = BIN.INPUT and
corresponding BI IDLE (PAGE 180) is closed. This logical output (Source) can be configured to corresponding
J1939 output (e.g. Idle Speed Select in Volvo-IndustrialD12 Aux).
Idle Sw
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 26
Description
Constant value that can be configured to any output (e.g. CurrentGear in Volvo-PRP).
Logical 0
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 27
Description
Constant value that can be configured to any output (e.g. CurrentGear in Volvo-PRP).
Logical 1