InteliDrive DCU Industrial 3.4.0 Global Guide
223
Related FW 3.4.0 Related applications AS, SS
Comm object
Description
Intercontroller communication error.
OthrCommEr
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object
Description
Charger fail detection. D+ output current is limited to cca 300 mA.
Guaranteed level for signal Charging OK = 90% of supply voltage.
There are three possible conditions for stop engine cranking: Starting RPM, StartingPOil and D+ function
(when ENABLED). Starter goes off when any of these conditions becomes valid.
ChrgAlternFail
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object
Description
Engine stop fail indication. Stop fail: engine does not reach 0 RPM after stop command within Stop Time
(page 120).
Stop Fail
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 779
Description
Engine overspeed indication.
Overspeed
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object
Description
Under speed indication.
Underspeed
6 back to List of LBO

Table of Contents