User’s Manual EM11A015B
intelligent Touch Manager
110
• When Representative suction temperature – Representative setpoint (Heat) > Thermal difference + 0.5,
operation mode is changed from Heat to Cool
• When Representative setpoint (Cool) – Representative suction temperature > Thermal difference + 0.5,
operation mode is changed from Cool to Heat
°C
Representative setpoint (Cool)
3°C
Representative setpoint (Heat)
<When the thermal difference is 2°C>
2°C
0.5°C
0.5°C
Representative setpoint (Heat) +
Thermal difference in (2°C) + 0.5
Representative setpoint (Cool) –
Thermal difference in (2°C) – 0.5
When the thermal difference is 2°C
Cooling mode Heating mode
Heating mode Cooling mode
Heating mode Heating modeCooling mode
Representative
suction temperature
• When Representative suction temperature – Representative setpoint (Heat) > Thermal difference + 1,
operation mode is changed from Heat to Cool
• When Representative setpoint (Cool) – Representative suction temperature > Thermal difference + 1,
operation mode is changed from Cool to Heat
°C
Representative setpoint (Cool)
Representative setpoint (Heat) –
Thermal difference in (1°C) + 1
3°C
Representative setpoint (Heat)
<When the thermal difference is 1°C>
1°C
1°C
1°C
Representative setpoint (Cool) –
Thermal difference in (1°C) –1
When the thermal difference is 1°C
Representative
suction
temperature
Heating mode Cooling mode
Cooling mode Heating mode
Heating mode Heating modeCooling mode