User’s Manual EM11A015B
intelligent Touch Manager
156
3. Effect on Other Functions
Use of Switch as trigger Use of On/Off status for assessment
Central Monitoring
Setback Active
Treated as ON
Setback Inactive
Treated as OFF
Automatic
Control
Schedule
Pre-Cool/Pre-
Heat
Interlocking
Start order by Setback
Treated as start trigger
Stop order by Setback
Treated as stop trigger
Emergency
Stop
Auto
Changeover
Setback Active
Not treated as ON
Setback Inactive
Treated as OFF
Temperature
Limit
Setback Active
Treated as ON
Setback Inactive
Not treated as OFF
Sliding
Temperature
HMO
Setback Active
Not treated as ON
Setback Inactive
Treated as OFF
Timer
Extension
Start order by Setback
Not treated as start trigger
Stop order by Setback
Treated as stop trigger
Setback Active
Not treated as ON
Setback Inactive
Treated as OFF
Data
Management
Power
Proportional
Distribution
Setback Active
Treated as ON
Setback Inactive
Treated as OFF
Energy
Navigator
(Timer
Extension
sampling)
Setback Active
Not treated as ON
Setback Inactive
Treated as OFF
Operation
time trend
Setback Active
Treated as ON
Setback Inactive
Treated as OFF
Start/Stop
count trend
Start order by Setback
Treated as start trigger
Stop order by Setback
Treated as stop trigger