Table 36. Warning events (continued)
Event Code Message Text and Description Details and Solution
4091 Auto calibration of one or more modules
failed. Adjustment out of range
v The library must be recalibrated.
v Ensure that the library firmware is up to date.
v This event indicates that one or more of the
gray calibration targets on the library
magazines could not be used in calibration.
v Inspect the calibration targets in each module
and then repeat the auto-calibration routine
with the Management GUI.
4093 Could not obtain an IP address from DHCP
server.
v Check the network configuration settings and
check if the DHCP server is reachable.
v Use the network configuration menu or
unplug the network cable and plug it in after a
few seconds to trigger an automatic
reconfiguration of the network interface.
4095 Library test failed. Not enough valid
cartridges available for testing.
Load the cartridges into the library.
4098 System time synchronization with SNTP
failed.
Check for valid SNTP server address in Time
configuration. If correct, ensure that the server is
reachable from your network and not blocked by
a firewall.
4099 An unexpected reset of accessor was
detected.
Ensure that the spooling cable is fully seated in
the base module and connected correctly to the
accessor assembly. If the error recurs, replace the
accessor assembly.
4113 Move from drive failed. Check for labels or cartridge misalignments that
prevents the cartridge from coming out of the
slot or drive.
4117 Drive disabled because no power supply
available.
Remove all affected drives, insert, and power up
at least one power supply to the failing module.
Wait 10 seconds and put the drives back into the
module.
4119 Drive disabled because internal IP address
unknown.
v Remove affected drive, wait 10 seconds, and
put it back into the module.
v Restart Library stack.
4120 No empty drive available for system test. Make sure that at least one empty drive and one
compatible cartridge are available.
4121 No compatible media available for system
test.
Make sure that at least one empty drive and one
compatible cartridge are in the drive.
4122 No cartridge available for slot to slot
exerciser test.
Make sure that at least one cartridge and one
empty slot are in the library.
4123 No empty slot available for slot to slot
exerciser test.
Make sure that at least one cartridge and one
empty slot are in the library.
4124 Drive or media statistics could not be
retrieved when the tape was unloaded.
Check for more warning tickets. Replace media if
media-related tape alert flags reported.
4126 Cartridge was found in inaccessible slot of
lowermost unit.
Bottom slots from the lowermost unit are
inaccessible to the accessor. Place the cartridge in
an upper slot.
Troubleshooting 91