EasyManuals Logo

Delta VFD-M-D series User Manual

Delta VFD-M-D series
163 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #70 background imageLoading...
Page #70 background image
Chapter 5 Parameters|VFD-M-D Series
Revision Jan. 2007, MDE2, SW V1.05 5-37
2-16
I
P
2-15
Output
Frequency
Limit
2-17
Frequency Command
PG
+
-
+
+
+
Output Frequency
Speed Detection
2 - 22 Door Width Auto-tuning Frequency Unit: 0.01
Settings 0.10~400.0 Hz Factory Setting: 4.00
This parameter is the frequency of motor when using door width auto-tuning function.
2 - 23 Door Width Auto-tuning Function
Factory Setting: 00
Settings 00 Disable
01 Enable
The door width will be difference due to its application. For example, the door of the freight
elevator is much wider than passenger elevator. Therefore, it needs to have door width auto-
tuning function to measure the correct door width for the correct position and door open/close.
The procedure for the door width auto-tuning function
First, operate to the door from the door close complete position to the door open complete
position for measuring the door width. Then, close the door to the complete position for
confirming the door width.
Door close limit
0.0 %
Door open limit
100.0%
Close door (FWD)
Open door (REV)
Close door (FWD)
to make sure the position
of door close limit
measure door width
detect if door width is correct
After running this function, the value of door width will auto fill in Pr.2-24 and Pr.2-25.
When executing auto-tuning, the start/stop DC braking function is disabled.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD-M-D series and is the answer not in the manual?

Delta VFD-M-D series Specifications

General IconGeneral
BrandDelta
ModelVFD-M-D series
CategoryController
LanguageEnglish

Related product manuals