Chapter 5 Parameters|VFD-M-D Series
Revision Jan. 2007, MDE2, SW V1.05 5-61
Incorrect door open limit:
a. The signal for the door close limit is received before Pr.4-01 setting.
b. The signal for the door close limit isn’t received after Pr.4-03 setting.
Incorrect door close limit:
a. The signal for the door open limit is received before Pr.3-03 setting.
b. The signal for the door open limit isn’t received after Pr.3-05 setting.
When bit 1=1 and the torque for the door close exceeds Pr.4-10/4-12, it won’t re-open the door.
When Pr.6-00 to Pr.6-07 (multi-function outputs) is set to 23, the error signal will also be
outputted.