EDR-3000 IM02602003E
Parameter Description Setting range Default Menu path
Inverting 5 Inverting of the state of the assigned signal. Inactive,
Active
Inactive [Device Para
/Relay Outputs
/RO-5 X2
/RO 5]
Assignment 6 Assignment 1..n, Assignment
List
-.- [Device Para
/Relay Outputs
/RO-5 X2
/RO 5]
Inverting 6 Inverting of the state of the assigned signal. Inactive,
Active
Inactive [Device Para
/Relay Outputs
/RO-5 X2
/RO 5]
Assignment 7 Assignment 1..n, Assignment
List
-.- [Device Para
/Relay Outputs
/RO-5 X2
/RO 5]
Inverting 7 Inverting of the state of the assigned signal. Inactive,
Active
Inactive [Device Para
/Relay Outputs
/RO-5 X2
/RO 5]
DISARMED Ctrl Enables and disables the disarming of the relay outputs.
This is the first step of a two step process, to inhibit the
operation or the relay outputs. Please refer to
"DISARMED" for the second step.
Inactive,
Active
Inactive [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/DISARMED
/RO-5 X2]
Disarm Mode CAUTION! RELAYS DISARMED in order to safely
perform maintenance while eliminating the risk of taking
an entire process off-line. (Note: Zone Interlocking and
Supervision Contact cannot be disarmed). YOU MUST
ENSURE that the relays are ARMED AGAIN after
maintenance.
Permanent,
Timeout
Permanent [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/DISARMED
/RO-5 X2]
www.eaton.com 103