EasyManua.ls Logo

Eaton EDR 3000 - Page 115

Eaton EDR 3000
770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EDR-3000 IM02602003E
Parameter Description Setting range Default Menu path
Inverting 5 Inverting of the state of the assigned signal. Inactive,
Active
Inactive [Device Para
/Relay Outputs
/RO-5 X2
/RO 5]
Assignment 6 Assignment 1..n, Assignment
List
-.- [Device Para
/Relay Outputs
/RO-5 X2
/RO 5]
Inverting 6 Inverting of the state of the assigned signal. Inactive,
Active
Inactive [Device Para
/Relay Outputs
/RO-5 X2
/RO 5]
Assignment 7 Assignment 1..n, Assignment
List
-.- [Device Para
/Relay Outputs
/RO-5 X2
/RO 5]
Inverting 7 Inverting of the state of the assigned signal. Inactive,
Active
Inactive [Device Para
/Relay Outputs
/RO-5 X2
/RO 5]
DISARMED Ctrl Enables and disables the disarming of the relay outputs.
This is the first step of a two step process, to inhibit the
operation or the relay outputs. Please refer to
"DISARMED" for the second step.
Inactive,
Active
Inactive [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/DISARMED
/RO-5 X2]
Disarm Mode CAUTION! RELAYS DISARMED in order to safely
perform maintenance while eliminating the risk of taking
an entire process off-line. (Note: Zone Interlocking and
Supervision Contact cannot be disarmed). YOU MUST
ENSURE that the relays are ARMED AGAIN after
maintenance.
Permanent,
Timeout
Permanent [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/DISARMED
/RO-5 X2]
www.eaton.com 103

Table of Contents