EasyManua.ls Logo

Eaton EDR 3000 - Page 116

Eaton EDR 3000
770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EDR-3000 IM02602003E
Parameter Description Setting range Default Menu path
t-Timeout DISARM The relays will be armed again after expiring of this time.
Only available if: Mode = Timeout DISARM
0.00 - 300.00s 0.03s [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/DISARMED
/RO-5 X2]
Force Mode By means of this function the normal Relay Output States
can be overwritten (forced) in case that the Relay Output
is not in a disarmed state. The relays can be set from
normal operation (relay works according to the assigned
signals) to "force energized" or "force de-energized"
state.
Permanent,
Timeout
Permanent [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Force RO
/RO-5 X2]
t-Timeout Force The Output State will be set by force for the duration of
this time. That means, for the duration of this time, the
Relay Output does not show the state of the signals that
are assigned on it.
Only available if: Mode = Timeout DISARM
0.00 - 300.00s 0.03s [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Force RO
/RO-5 X2]
www.eaton.com 104

Table of Contents