Parameter Description Setting range Default Menu path
Start: 7 Start recording if the assigned signal is true. 1..n, Assignment
List
-.- [Device Para
/Recorders
/Waveform rec]
Start: 8 Start recording if the assigned signal is true. 1..n, Assignment
List
-.- [Device Para
/Recorders
/Waveform rec]
Auto overwriting If there is no more free memory capacity left, the oldest
file will be overwritten.
Inactive,
Active
Active [Device Para
/Recorders
/Waveform rec]
Post-trigger time The post trigger time is settable up to a maximum of 50%
of the Maximum file size setting. The post-trigger will be
the remaining time of the "Max file size" but at maximum
"Post-trigger time"
0 - 50% 20% [Device Para
/Recorders
/Waveform rec]
Pre-trigger time The pre trigger time is settable up to a maximum of 50%
of the Maximum file size setting.
0 - 50% 20% [Device Para
/Recorders
/Waveform rec]
Max file size The maximum storage capacity per record is 10 seconds,
including pre-trigger and post-trigger time. The waveform
recorder has a total storage capacity of 120 seconds.
0.1 - 10.0s 2s [Device Para
/Recorders
/Waveform rec]