EasyManua.ls Logo

Eaton EDR 3000 - Page 387

Eaton EDR 3000
770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EDR-3000 IM02602003E
Global Protection Parameters of the Switchgear/Breaker
Parameter Description Setting range Default Menu path
CinBkr-52a The breaker is in CLOSE-position if the state of the
assigned signal is true (52a).
1..n, Dig Inputs DI-4P X1.DI 1 [Control
/Bkr
/Pos Indicatrs
Wirng]
CinBkr-52b The breaker is in OPEN-position if the state of the
assigned signal is true (52b).
1..n, Dig Inputs DI-4P X1.DI 2 [Control
/Bkr
/Pos Indicatrs
Wirng]
Ready Breaker is ready for operation if the state of the assigned
signal is true. This digital input can be used by some
protective elements (if they are available within the
device) like Auto Reclosure (AR), e.g. as a trigger signal.
1..n, Dig Inputs -.- [Control
/Bkr
/Pos Indicatrs
Wirng]
Interl CLOSE1 Interlocking of the CLOSE command 1..n, Assignment
List
Wired Inputs.Bkr
Trouble-I
[Control
/Bkr
/Interlockings]
Interl CLOSE2 Interlocking of the CLOSE command 1..n, Assignment
List
-.- [Control
/Bkr
/Interlockings]
Interl CLOSE3 Interlocking of the CLOSE command 1..n, Assignment
List
-.- [Control
/Bkr
/Interlockings]
Interl OPEN1 Interlocking of the OPEN command 1..n, Assignment
List
-.- [Control
/Bkr
/Interlockings]
Interl OPEN2 Interlocking of the OPEN command 1..n, Assignment
List
-.- [Control
/Bkr
/Interlockings]
Interl OPEN3 Interlocking of the OPEN command 1..n, Assignment
List
-.- [Control
/Bkr
/Interlockings]
SC CLOSE Switching CLOSE Command, e.g. the state of the Logics
or the state of the digital input
1..n, DI-LogicList -.- [Control
/Bkr
/Ex OPEN/CLOSE
Cmd]
www.eaton.com 375

Table of Contents

Related product manuals