EDR-3000 IM02602003E
Parameter Description Setting range Default Menu path
SC OPEN Switching OPEN Command, e.g. the state of the Logics
or the state of the digital input
1..n, DI-LogicList -.- [Control
/Bkr
/Ex OPEN/CLOSE
Cmd]
t-TripCmd Minimum hold time of the OPEN-command (Breaker,
load break switch)
0 - 300.00s 0.2s [Control
/Bkr
/Trip Manager]
Latched Defines whether the Relay Output will be Latched when it
picks up.
Inactive,
Active
Inactive [Control
/Bkr
/Trip Manager]
Ack TripCmd Ack TripCmd 1..n, Assignment
List
-.- [Control
/Bkr
/Trip Manager]
Trigger1 Open Command to the Breaker if the state of the
assigned signal becomes true.
1..n, Trip Cmds 50P[1].TripCmd [Control
/Bkr
/Trip Manager]
Trigger2 Open Command to the Breaker if the state of the
assigned signal becomes true.
1..n, Trip Cmds 50P[2].TripCmd [Control
/Bkr
/Trip Manager]
Trigger3 Open Command to the Breaker if the state of the
assigned signal becomes true.
1..n, Trip Cmds 51P[1].TripCmd [Control
/Bkr
/Trip Manager]
Trigger4 Open Command to the Breaker if the state of the
assigned signal becomes true.
1..n, Trip Cmds 50X[1].TripCmd [Control
/Bkr
/Trip Manager]
Trigger5 Open Command to the Breaker if the state of the
assigned signal becomes true.
1..n, Trip Cmds 50X[2].TripCmd [Control
/Bkr
/Trip Manager]
Trigger6 Open Command to the Breaker if the state of the
assigned signal becomes true.
1..n, Trip Cmds 51X[1].TripCmd [Control
/Bkr
/Trip Manager]
Trigger7 Open Command to the Breaker if the state of the
assigned signal becomes true.
1..n, Trip Cmds 50R[1].TripCmd [Control
/Bkr
/Trip Manager]
www.eaton.com 376