Breaker Wear Signals (Output States)
Signal Description
Operations Alarm Signal: Service Alarm, too many Operations
Isum Intr trip: IA Signal: Maximum permissible Summation of the interrupting (tripping) currents exceeded: IA
Isum Intr trip: IB Signal: Maximum permissible Summation of the interrupting (tripping) currents exceeded: IB
Isum Intr trip: IC Signal: Maximum permissible Summation of the interrupting (tripping) currents exceeded: IC
Isum Intr trip Signal: Maximum permissible Summation of the interrupting (tripping) currents exceeded in at
least one phase.
Res TripCmdCr Signal: Resetting of the Counter: total number of trip commands
Res Isum trip Signal: Reset summation of the tripping currents
WearLevel Alarm Signal: Breaker Wear curve Alarm
WearLevel Lockout Signal: Breaker Wear Curve Lockout Level
Res Bwear Curve Signal: Reset of the Breaker Wear maintenance curve.
Isum Intr ph Alm Signal: Alarm, the per hour Sum (Limit) of interrupting currents has been exceeded.
Res Isum Intr ph Alm Signal: Reset of the Alarm, "the per hour Sum (Limit) of interrupting currents has been exceeded".