EDR-3000 IM02602003E
Breaker Wear Counter Values
Value Description Default Size Menu path
TripCmd Cr Counter: Total number of trips of the switchgear
(breaker, load break switch…). Resettable with
Total or All.
0 0 - 200000 [Operation
/Count and RevData
/Control
/Bkr]
Breaker Wear Values
Value Description Default Size Menu path
Isum trip IA Summation of the tripping currents phase 0.00A 0.00 - 1000.00A [Operation
/Count and RevData
/Control
/Bkr]
Isum trip IB Summation of the tripping currents phase 0.00A 0.00 - 1000.00A [Operation
/Count and RevData
/Control
/Bkr]
Isum trip IC Summation of the tripping currents phase 0.00A 0.00 - 1000.00A [Operation
/Count and RevData
/Control
/Bkr]
Isum Intr per hour Sum per hour of interrupting currents. 0.00kA 0.00 - 1000.00kA [Operation
/Count and RevData
/Control
/Bkr]
Bkr OPEN capacity CB OPEN capacity. 100% means, that the
breaker is to be maintenanced.
0.0% 0.0 - 100.0% [Operation
/Count and RevData
/Control
/Bkr]